ABSTRACT
This paper presents the optimisation and extension of the primary AC power standard of the Physikalisch-Technische Bundesanstalt. The newly developed measurement system allows precise measurements of voltages up to 480 V and currents up to 100 A in a frequency range from 16.67 to 400 Hz. To achieve this, the components of the system have been thoroughly optimised and, in some cases, completely redeveloped. The modernisation ensures long-term operational stability, increases reliability and improves both measurement accuracy and system stability. At the same time, the measurement uncertainty is reduced over the entire frequency range.
The ac primary power standard is of central importance as it forms the basis for precise and traceable measurements of electrical power. Consequently, it supports many industrial applications, the energy transition, innovation and research and ensures compliance with legal and international standards. To achieve the high accuracy, the voltage and current measuring sensors, electronics and sampling method were newly developed and implemented. In addition, specially customised control software was developed.
The new developed current sensor is based on an electronically error-compensated and shielded two-core transformer design with attained errors in the order of 10-7. The modular design allows the two main components - the current transformer and the measuring resistor - to be calibrated separately using traceable reference systems. The combined ratio and phase errors of the current transformer and the errors and phase deviations of the measuring resistor define the combined error of the transformer. To increase measurement accuracy and stability, the active sensing resistor is thermostatically controlled to significantly minimise the thermal effects induced by the current. These optimisations reduce the measurement uncertainty in the current path by a factor of about 3. Another advancement is the newly developed inductive voltage divider, which act as the voltage sensor in the measurement system. It is based on a two stage principle. By employing symmetry in the 3D-printed winding support and optimized winding technology, a symmetrical distribution of winding leads is achieved. This results in measurement deviations of less than 0.3 µV/V and a reduction of measurement uncertainty in the voltage path by a factor of 4.
An innovative sampling method utilizing two Keysight 3458A digital voltmeters has been developed to sample the output voltages from the measuring sensors. This approach enables the simultaneous acquisition with an automated swapping of the sampler input inputs. This in turn cancels the mismatch between the two DVMs and reduces the measurement uncertainty of the sampling process. To manage the sampling process, a novel sampling controller has been designed, allowing flexible synchronization through various methods, including an internal quartz oscillator or external signals via TTL or fiber-optic interfaces operating at different frequencies.
This work highlights and demonstrate the importance of a continuous development and modernisation to ensure long-term operational safety and reliability of a primary standard at NMI level. In particular, the use of 3D printing processes shows great potential for increasing efficiency and gaining improved precision even in well-established technologies such as the fabrication of inductive voltage dividers.
CITE THIS POSTER
Include:
Dubowik, A., & Mohns, E.. (2025). Modernisation and Optimisation of PTB's Primary AC Power Standard. 150th anniversary of the Metre Convention — From Units to the Universe. Palais des congrès de Versailles, Versailles, France. Bureau International des Poids et Mesures (BIPM). https://doi.org/10.59161/PWAK8545
Dubowik, Alexander, and Enrico Mohns. “Modernisation and Optimisation of PTB's Primary AC Power Standard.”. 150th anniversary of the Metre Convention — From Units to the Universe, 2025, Palais des congrès de Versailles, Versailles, France, Bureau International des Poids et Mesures (BIPM). DOI: 10.59161/PWAK8545
Dubowik, Alexander, Enrico Mohns. 2025. “Modernisation and Optimisation of PTB's Primary AC Power Standard.”. 150th anniversary of the Metre Convention — From Units to the Universe, Palais des congrès de Versailles, Versailles, France. Bureau International des Poids et Mesures (BIPM). https://doi.org/10.59161/PWAK8545
@inproceedings{dubowik2025modernisation_and_op,
author = {Dubowik, Alexander and Mohns, Enrico},
title = {Modernisation and Optimisation of PTB's Primary AC Power Standard},
booktitle = {150th anniversary of the Metre Convention — From Units to the Universe},
year = {2025},
address = {Palais des congrès de Versailles, Versailles, France},
publisher = {Bureau International des Poids et Mesures (BIPM)},
doi = {10.59161/PWAK8545},
url = {https://thebipm150.org/poster-page/10euhx5},
}
TY - CONF
AU - Dubowik, Alexander
AU - Mohns, Enrico
TI - Modernisation and Optimisation of PTB's Primary AC Power Standard
T2 - 150th anniversary of the Metre Convention — From Units to the Universe
PB - Bureau International des Poids et Mesures (BIPM)
PY - 2025
CY - Palais des congrès de Versailles, Versailles, France
DO - 10.59161/PWAK8545
UR - https://thebipm150.org/poster-page/10euhx5
ER -